ASi-3 PROFIsafe via PROFINET Gateway with integrated Safety Monitor, 2 ASi-3 masters, integrated decoupling, max. 4 A per ASi circuit, ASi current measurement in the gateway, 6 digital inputs or 3 x 2 channels safe inputs (SIL 3, cat. 4), expandable to max. 62 x 2 channels safe inputs, 1922 x 2 channels safe inputs in max. configuration, 6 release circuits (6 x electronic safe outputs), expandable to max. 64 safe outputs, 1984 safe outputs in max. configuration, PROFIsafe (F-CPU and Safe Link, diagnostic and configuration via PROFINET or Ethernet diagnostic interface, duplicate address recognition, ASi fault detector, programming in C optional, IP20
ASi-3 PROFIsafe via PROFINET Gateway with integrated Safety Monitor, 2 ASi masters (BWU3367)
SKU: BWU3367
Category: Safety Monitor
Fieldbus interface | |
---|---|
Safety communication | |
Model | |
Inputs Safety, SIL 3, Cat. 4 | |
Outputs Safety, SIL 3, cat. 4 |