Replacement for PD600, contact us upon purchase.
- Real time clock with battery backup.
- 64 – 1024 kBytes in circuit programmable FLASH memory for user program.
- 128 – 2048 kBytes in circuit programmable FLASH memory for user data.
- 64 – 992 kBytes RAM memory with battery backup for user data (2 kBytes of RAM reserved for system variables).
- Built-in replaceable lithium battery.
- LED state indicators.
- Low power consumption.
- Process-Pascal programmable.
- Automatic checksum control of program memory after each Reset.
- EMC approved (89/336/EEC).
APPLICATION
A PD600B DPI is used to provide local programmable intelligence and act as a gateway between the standard P-NET system (RS-485) and the local cluster via Light-Link P-NET.
It uses either the BM002, or the BM010 Base Module.
The PD600B DPI is programmed in Process-Pascal, which is an extension of standard Pascal, allowing easy declaration and utilisation of P-NET variables and objects. Programs are developed and compiled on a standard PC, then downloaded directly via a P-NET interface. Program code can be downloaded to FLASH memory.
SPECIFICATIONS
Communication
The PD600B has 2 standard P-NET Communication Channels.
Channel 1 is a standard P-NET RS485 communication channel for communicating with other P-NET devices outside the cluster, i.e. the rest of the system.
Channel 2 is a P-NET Light-Link communication channel intended for communicating with other locally mounted P-NET devices using the optical Light-Link interface.
Memory
Program FLASH: 64 – 1024 kBytes
Data FLASH: 128 – 2048 kBytes
RAM 64 – 992 kBytes
*) 2 kBytes of RAM reserved for system variables. |
Power Specifications
Power Supply DC: nom. 24.0 V
min. 15.0 V
max. 32.0 V
Ripple: max. 5 %
Power consumption @ 24 VDC
Operating: max. 50 mA
Current at power up: max. 100 mA
Battery Backup (RAM and RTC)
Replaceable battery (Panasonic) BR1632
Replace battery every 5 years.
If the operating ambient temperature is over 50 °C,
replace battery more frequently.
Backup time @ 25 °C typ. 1 year
Environmental Conditions
Ambient Temperature
Operating temperature: ÷25 °C – 70 °C
Storage temperature: ÷40 °C – 85 °C
Humidity
Relative humidity: max. 95 %
Real Time Clock
Accuracy: Deviation is approx. 3 minutes per month over the full
temperature range.
Deviation is approx. 1 minute per month at 25 °C
Approvals
EMC EN61000-6-2, EN61000-6-3
Vibration IEC 60068-2-6
Frequency range: 2-100 Hz
Frequency / amplitude: 2-10 Hz: ± 5.0 mm
10-100 Hz: ± 2g
Sweep rate: max. 1 octave/min
Number of axes: 3 mutually perpendicular
Mounting requirements
The PD600B DPI must be mounted in a metal enclosure/panel.