Max. measurement error
Volume flow (liquid): ±0.75 %
Volume flow (optional): ±0.65 %
Volume flow (steam, gas): ±1.00 %
Mass flow (saturated steam): ±1.7% (temperature compensated); ±1.5% (temperature/pressure compensated)
Mass flow (superheated steam, gas): ±1.5 (temperature/pressure compensated); ±1.7% (temperature compensated + external pressure compensation)
Mass flow (liquid): ±0.85%
Measuring range
Liquid: 0.076 to 2100 m³/h (0.045 to 1300 ft³/min)
depending on medium: water with 1 bar a, 20 °C (14.5 psi a, 68° F)
Steam, gas: 0.39 to 28000 m³/h (0.23 to 17000 ft³/min)
depending on medium: steam with 180 °C, 10 bar a (356 °F, 145 psi a); air with 25 °C, 4.4 bar a (77 °F, 63.8 psi a)
Medium temperature range
Standard: –40 to +260 °C (–40 to +500 °F)
High/low temperature (option): –200 to +400 °C (–328 to +752 °F)
Max. process pressure
PN 100, Class 600, 20K
Wetted materials
Measuring tube: 1.4408 (CF3M); CX2MW similar to Alloy C22, 2.4602